N2XS2Y Cable

N2XS2Y cable is a medium voltage power cable that meets international standards and is designed for efficient and reliable power transmission. Its core is insulated with cross-linked polyethylene (XLPE) insulation, which provides excellent electrical properties and thermal stability and is suitable for use in power systems with rated voltages of 12/20 kV or 18/30 kV. The construction of the N2XS2Y model manufactured by ZMS Cables consists of a high-purity copper conductor, a double-layered, semi-conductive shield, and a braided shield of copper wires, which ensures uniform distribution of the electric field and excellent EMC compatibility. The outer jacket is made of weather-resistant, flame-retardant PVC, providing excellent mechanical protection and environmental suitability for direct burial, conduit, or indoor laying.

N2XS2Y Cable Structure

N2xs2y cable medium voltage
N2XS2Y cable structure
Get A Free Quotation
Conductor Material: annealed copper conductor (Class 2 stranded copper according to IEC 60228)
Shape: round tightly pressed structure to improve filling rate and mechanical strength
Conductor Shield Semi-conductive layer: extruded semi-conductive material, smooth electric field distribution
Insulation Material: Cross-linked polyethylene (XLPE)
Thickness: customized according to voltage level (e.g. 12/20 kV, 18/30 kV)
Insulation Shield Semi-conductive layer: continuous electric field protection with conductor shielding
Metal Shield Structure: Concentric copper wire braid or copper tape winding, providing short-circuit current paths
Function: Electromagnetic shielding, mechanical protection
Outer Jacket Material: PVC (weather resistant, flame retardant, UV resistant)
Color: usually black or red, can be customized

N2XS2Y Meaning

According to VDE/IEC Standard Naming Rules
N: VDE compliant (German Association of Electrical Engineers standard)2X: Cross-linked polyethylene (XLPE) insulation
S: Copper wire shielding (concentric layers or braided shielding)2Y: Polyvinyl chloride (PVC) outer jacket

Main Performance Features

Electrical Properties: high dielectric strength, withstand voltage ratings up to 18/30 kV, low dielectric loss
Thermal Stability: long-term operating temperature of 90 ° C, short-circuit temperature of 250 ° C (IEC 60502-2)
Mechanical Strength: XLPE creep resistance, sheath wear resistance, adapt to direct burial, pipe laying
Environmental Resistance: PVC sheath moisture, oil, acid and alkali corrosion resistance, suitable for wet or polluted environments
Safety Certification: RoHS compliant, halogen-free (optional low-smoke halogen-free jacket)

Suitable for the Following Scenarios

Fixed Laying: underground cable trench, tunnel, indoor power distribution system
Industrial Field: medium voltage distribution network of petrochemical plants, mines, and power stations.
Infrastructure: subways, airports, hospitals, and other places that require high reliability of power supply.

N2XS2Y Cable Specification

Model NumberCore NumberRated Voltage (U/U)Conductor Cross Section (mm²)Current-Carrying Capacity (A)Outer Diameter (mm)Weight (kg/km)
N2XS2Y 1×95112/20 kV9532026.52,100
N2XS2Y 1×150112/20 kV15039029.52,900
N2XS2Y 1×240112/20 kV24048033.54,100
N2XS2Y 1×400112/20 kV40060038.55,800
N2XS2Y 3×50312/20 kV5022045.54,200
N2XS2Y 3×95312/20 kV9529051.55,800
N2XS2Y 3×150312/20 kV15036057.57,500
N2XS2Y 3×240312/20 kV24044064.510,200
N2XS2Y 3×400312/20 kV40055073.514,500
N2XS2Y 1×50118/30 kV5024025.51,600
N2XS2Y 1×95118/30 kV9531028.52,300
N2XS2Y 1×150118/30 kV15038031.53,200
N2XS2Y 1×240118/30 kV24047035.54,500
N2XS2Y 1×400118/30 kV40059040.56,300
N2XS2Y 3×50318/30 kV5021047.54,500
N2XS2Y 3×95318/30 kV9528053.56,200
N2XS2Y 3×150318/30 kV15035059.58,000
N2XS2Y 3×240318/30 kV24043066.510,800
N2XS2Y 3×400318/30 kV40054075.515,200

NOTE:
1. The flow-carrying capacity is affected by the laying method (direct burial, pipeline, in air) and ambient temperature, and needs to be adjusted according to the actual working conditions.
2. If armored type (such as N2XS2Y-FR) is required, the outer diameter and weight will be increased.
3. The above data is for general reference, we suggest contacting ZMS Cable for detailed information.

General International Standards

Standard TypeStandard NumberContent Coverage
German StandardVDE 0276-620Medium Voltage Cable Construction and Testing Requirements
International StandardIEC 60502-2Specification for 1~30 kV extruded insulated cables
British StandardBS 6622Power cable performance and installation requirements
China StandardGB/T 12706.2-2020Rated voltage 6~35 kV cross-linked polyethylene cable

ZMS Reminds Selection Notes

Voltage Matching: select 12/20 kV or 18/30 kV according to the highest system voltage.
Laying Method: direct buried need to choose steel belt armored models (such as N2XS2Y-FR), non-armored applicable to pipeline
Ambient Temperature: high-temperature environment is recommended to choose heat-resistant PVC or LSZH sheath variants

Compared with YJV22 and other models, N2XS2Y model cables pay more attention to shielding performance and European standard compatibility, which is very suitable for export projects.
ZMS Customized Service: special sheath enhancement versions such as Flame Retardant (FR), Termite Resistant, and Rodent Bite Resistant are available.

    We Provide High Quality Products and The Most Professional Cable Accessories Project Solutions.