N2XS2Y cable is a medium voltage power cable that meets international standards and is designed for efficient and reliable power transmission. Its core is insulated with cross-linked polyethylene (XLPE) insulation, which provides excellent electrical properties and thermal stability and is suitable for use in power systems with rated voltages of 12/20 kV or 18/30 kV. The construction of the N2XS2Y model manufactured by ZMS Cables consists of a high-purity copper conductor, a double-layered, semi-conductive shield, and a braided shield of copper wires, which ensures uniform distribution of the electric field and excellent EMC compatibility. The outer jacket is made of weather-resistant, flame-retardant PVC, providing excellent mechanical protection and environmental suitability for direct burial, conduit, or indoor laying.
Table of Contents
ToggleN2XS2Y Cable Structure


Conductor | Material: annealed copper conductor (Class 2 stranded copper according to IEC 60228) |
Shape: round tightly pressed structure to improve filling rate and mechanical strength | |
Conductor Shield | Semi-conductive layer: extruded semi-conductive material, smooth electric field distribution |
Insulation | Material: Cross-linked polyethylene (XLPE) |
Thickness: customized according to voltage level (e.g. 12/20 kV, 18/30 kV) | |
Insulation Shield | Semi-conductive layer: continuous electric field protection with conductor shielding |
Metal Shield | Structure: Concentric copper wire braid or copper tape winding, providing short-circuit current paths |
Function: Electromagnetic shielding, mechanical protection | |
Outer Jacket | Material: PVC (weather resistant, flame retardant, UV resistant) |
Color: usually black or red, can be customized |
N2XS2Y Meaning
According to VDE/IEC Standard Naming Rules | |
N: VDE compliant (German Association of Electrical Engineers standard) | 2X: Cross-linked polyethylene (XLPE) insulation |
S: Copper wire shielding (concentric layers or braided shielding) | 2Y: Polyvinyl chloride (PVC) outer jacket |
Main Performance Features
Electrical Properties: high dielectric strength, withstand voltage ratings up to 18/30 kV, low dielectric loss
Thermal Stability: long-term operating temperature of 90 ° C, short-circuit temperature of 250 ° C (IEC 60502-2)
Mechanical Strength: XLPE creep resistance, sheath wear resistance, adapt to direct burial, pipe laying
Environmental Resistance: PVC sheath moisture, oil, acid and alkali corrosion resistance, suitable for wet or polluted environments
Safety Certification: RoHS compliant, halogen-free (optional low-smoke halogen-free jacket)
Suitable for the Following Scenarios
Fixed Laying: underground cable trench, tunnel, indoor power distribution system
Industrial Field: medium voltage distribution network of petrochemical plants, mines, and power stations.
Infrastructure: subways, airports, hospitals, and other places that require high reliability of power supply.
N2XS2Y Cable Specification
Model Number | Core Number | Rated Voltage (U₀/U) | Conductor Cross Section (mm²) | Current-Carrying Capacity (A) | Outer Diameter (mm) | Weight (kg/km) |
N2XS2Y 1×95 | 1 | 12/20 kV | 95 | 320 | 26.5 | 2,100 |
N2XS2Y 1×150 | 1 | 12/20 kV | 150 | 390 | 29.5 | 2,900 |
N2XS2Y 1×240 | 1 | 12/20 kV | 240 | 480 | 33.5 | 4,100 |
N2XS2Y 1×400 | 1 | 12/20 kV | 400 | 600 | 38.5 | 5,800 |
N2XS2Y 3×50 | 3 | 12/20 kV | 50 | 220 | 45.5 | 4,200 |
N2XS2Y 3×95 | 3 | 12/20 kV | 95 | 290 | 51.5 | 5,800 |
N2XS2Y 3×150 | 3 | 12/20 kV | 150 | 360 | 57.5 | 7,500 |
N2XS2Y 3×240 | 3 | 12/20 kV | 240 | 440 | 64.5 | 10,200 |
N2XS2Y 3×400 | 3 | 12/20 kV | 400 | 550 | 73.5 | 14,500 |
N2XS2Y 1×50 | 1 | 18/30 kV | 50 | 240 | 25.5 | 1,600 |
N2XS2Y 1×95 | 1 | 18/30 kV | 95 | 310 | 28.5 | 2,300 |
N2XS2Y 1×150 | 1 | 18/30 kV | 150 | 380 | 31.5 | 3,200 |
N2XS2Y 1×240 | 1 | 18/30 kV | 240 | 470 | 35.5 | 4,500 |
N2XS2Y 1×400 | 1 | 18/30 kV | 400 | 590 | 40.5 | 6,300 |
N2XS2Y 3×50 | 3 | 18/30 kV | 50 | 210 | 47.5 | 4,500 |
N2XS2Y 3×95 | 3 | 18/30 kV | 95 | 280 | 53.5 | 6,200 |
N2XS2Y 3×150 | 3 | 18/30 kV | 150 | 350 | 59.5 | 8,000 |
N2XS2Y 3×240 | 3 | 18/30 kV | 240 | 430 | 66.5 | 10,800 |
N2XS2Y 3×400 | 3 | 18/30 kV | 400 | 540 | 75.5 | 15,200 |
NOTE:
1. The flow-carrying capacity is affected by the laying method (direct burial, pipeline, in air) and ambient temperature, and needs to be adjusted according to the actual working conditions.
2. If armored type (such as N2XS2Y-FR) is required, the outer diameter and weight will be increased.
3. The above data is for general reference, we suggest contacting ZMS Cable for detailed information.
General International Standards
Standard Type | Standard Number | Content Coverage |
German Standard | VDE 0276-620 | Medium Voltage Cable Construction and Testing Requirements |
International Standard | IEC 60502-2 | Specification for 1~30 kV extruded insulated cables |
British Standard | BS 6622 | Power cable performance and installation requirements |
China Standard | GB/T 12706.2-2020 | Rated voltage 6~35 kV cross-linked polyethylene cable |
ZMS Reminds Selection Notes
Voltage Matching: select 12/20 kV or 18/30 kV according to the highest system voltage.
Laying Method: direct buried need to choose steel belt armored models (such as N2XS2Y-FR), non-armored applicable to pipeline
Ambient Temperature: high-temperature environment is recommended to choose heat-resistant PVC or LSZH sheath variants
Compared with YJV22 and other models, N2XS2Y model cables pay more attention to shielding performance and European standard compatibility, which is very suitable for export projects.
ZMS Customized Service: special sheath enhancement versions such as Flame Retardant (FR), Termite Resistant, and Rodent Bite Resistant are available.